DaqDConfigPort

>Psychtoolbox>PsychHardware>Daq

err=DaqDConfigPort(DeviceIndex
USB-1208FS: Configure digital port. This command sets the direction of
the DIO port to input or output.
DeviceIndex” is a small integer, the array index specifying which HID
device in the array returned by PsychHID(‘Devices’) is interface 0
of the desired USB-1208FS box.
“port” 0 = port A, 1 = port B
“direction” 0 = output, 1 = input

USB-1608FS: has only one port, so second argument is meaningless. If three
arguments are passed and device is a 1608FS, second argument is ignored.
Function could be made more efficient if a separate one were written for
1608FS, but I’m guessing this function will never be used at a time when
maximal speed is an overarching requirement.
See also Daq, DaqFunctions, DaqPins, DaqTest, PsychHidTest.

USB-1024LS: Has three ports: 1 = port A, 4 = port B, 10 = port C (the sum
of: 8 = portC low, 2 = portC high). The card is verified to work well with
using port A or B for output and port C as a whole for input.

4/15/05 dgp Wrote it.
12/18/07 mpr extended for 1608
1/11/08 mpr swept through trying to improve consistency across daq
functions
5/22/08 mk Add (untested!) support for USB-1024LS box.
5/23/08 mk Add caching for HID device list.
8/12/2010 sdv Fixed error when other HID devices have short names
07/31/16 mk Remove experimental note about 1024LS. It’s tested and known to work.

Path   Retrieve current version from GitHub | View changelog
Psychtoolbox/PsychHardware/Daq/DaqDConfigPort.m